Most VLF buyers compare kilovolts. The specification that decides whether a set works is the load capability at the test voltage you will actually apply.
A VLF hipot tester applies an AC voltage at very low frequency, typically 0.1 Hz or lower, so that the capacitive current of a cable stays small enough for a portable set to supply. That single idea explains both the appeal and the confusion: a set rated for 80 kV may not be able to test a long feeder at 80 kV, and a set rated for 50 kV may be the correct choice for a 33 kV cable if the runs are short. Choosing well means reading the load capability, not the headline voltage.
Every VLF purchase answers five questions, and they interact:
A set that wins on the first question and loses on the second is the most common buying error in this category.
Write down the cables you will actually test, and for each one record:
Two numbers come out of this list: the highest test voltage you need, and the largest capacitance you need to energise at that voltage. Those two numbers select the instrument.
At low frequency, the cable is essentially a capacitor, and the current the set must supply follows the capacitive reactance:
Test current and reactive power
I = 2 × π × f × C × U
Q = 2 × π × f × C × U²
I: current the set must supply, in amperes (RMS)
f: test frequency, in hertz (0.1, 0.05, 0.02 …)
C: capacitance of the cable under test, in farads
U: RMS test voltage, in volts - use RMS consistently, never peak
Q: reactive power, in var (1 kvar = 1,000 var)
Both relations assume a sinusoidal test voltage and a cable that behaves as a linear capacitor. A VLF set with low waveform distortion and a stable frequency comes close to that assumption; a distorted waveform or a set operating at its limit does not, and the current it can actually deliver should be taken from the manufacturer's capability data rather than from the formula alone.
Because frequency appears in the numerator, lowering it reduces both current and reactive power in proportion. That is why a 50 kV set can be built around a 40 kg booster: at 0.1 Hz the current is roughly one five-hundredth of what the same cable would draw at 50 Hz.
Take a 2 km feeder of 0.35 µF/km, so C = 0.7 µF, and use 19 kV RMS as the test voltage. That value happens to equal 3U0 for an 11 kV cable (U0 = 11 / √3 = 6.35 kV), which makes it a convenient illustration - not a recommendation. Test levels differ between installation, acceptance and maintenance testing, and the applicable value must come from the edition of IEEE 400.2 in force and from the project specification.
At 0.1 Hz
I = 2 × 3.1416 × 0.1 × 0.7×10⁻⁶ × 19,000 = 8.4 mA
Q = U × I = 19,000 × 0.00836 = 159 var
Now take a 10 km run of the same cable, C = 3.5 µF:
At 0.1 Hz, then 0.05 Hz
I at 0.1 Hz = 2 × 3.1416 × 0.1 × 3.5×10⁻⁶ × 19,000 = 41.8 mA (Q ≈ 794 var)
I at 0.05 Hz = 2 × 3.1416 × 0.05 × 3.5×10⁻⁶ × 19,000 = 20.9 mA (Q ≈ 397 var)
If a set had a 30 mA output limit - a hypothetical figure for this illustration, not a product rating - it could not hold the first case, while at 0.05 Hz the same limit would be inside.
This is why frequency range is a capability, not a convenience. A fixed-frequency set that cannot drop to 0.05 Hz will refuse the long feeder that a sweeping set handles without operator intervention.
VLF ratings are published as capacitance against voltage, not as one number, and the figure falls as the voltage rises. The rows below are taken from current product documentation; each belongs to a specific model and, in the sweeping models, to an automatic frequency range rather than a single frequency.
| Model | Rated output | Published load capability |
|---|---|---|
| XHDP 80 kV (60/80 kV build) | 60 kV peak; 80 kV peak | ≤ 5 µF at 60 kV; ≤ 6 µF up to 50 kV and ≤ 4 µF above 50 kV at 80 kV |
| XHDP-80M (auto sweep) | 30, 50, 60, 80 kV peak | ≤ 10 µF at 30 kV; ≤ 6 µF at 50 kV; ≤ 5 µF at 60 kV; ≤ 6 µF up to 50 kV and ≤ 4 µF above 50 kV at 80 kV |
| XHDPJ diagnostic series | 30, 50, 60, 80/90 kV peak | ≤ 10 µF at 30 kV and 50 kV; ≤ 5 µF at 60 kV; ≤ 10 µF up to 50 kV and ≤ 4 µF above 50 kV at 80/90 kV |
| XHDP-50 (three fixed frequencies) | 50 kV peak | ≤ 1.1 µF at 0.1 Hz; ≤ 2.2 µF at 0.05 Hz; ≤ 5.5 µF at 0.02 Hz |
Three cautions apply to every row. The maximum capacitance is not available at the maximum voltage. Values differ between models even at the same nominal rating, because the booster arrangement differs. And where the documentation states a capability for an automatic sweep without stating the frequency at which it applies, the figure should be confirmed with the manufacturer for the frequency you intend to use - the XHDP-50 table is the clearest case, because it gives a separate capacitance for each of its three fixed frequencies.
Most VLF sets produce a single-phase output, and the usual procedure is to test one phase at a time with the other two earthed. The capacitance the set sees in that arrangement is not simply one third of a measured three-phase total: it depends on the cable construction and on how the conductors, screens and earth are connected during the test.
In a three-core cable with a common screen, the phase-to-screen capacitance of one conductor is influenced by the other two conductors and by their earthing. In three single-core cables, each phase has its own screen, and testing one phase with the other two earthed gives a different circuit from testing all three together. Use measured or data-sheet values for the connection actually adopted, and follow the manufacturer's guidance where the capacitance is close to the set's limit.
Energising all three phases together requires a different connection and substantially more current than a single-phase test, and it is rarely used for routine withstand testing. If a specification asks for it, size the set from the total capacitance in that arrangement, not from a per-phase figure.
Lowering the frequency reduces the current, but it also reduces the number of voltage cycles applied in a given time. A 15-minute test at 0.1 Hz applies 90 cycles; the same 15 minutes at 0.02 Hz applies 18 cycles. The two are not equivalent tests, and one cannot be substituted for the other by adjusting the clock.
Some specifications state duration in minutes at a stated frequency; others state a number of cycles, or give separate durations for different frequencies. Read the requirement as written, and do not convert one form into the other unless the standard allows it. A set that lowers frequency automatically must still be programmed with the duration the specification requires at that frequency.
This is also a throughput consideration. If the specification defines duration in minutes, the test takes the same wall-clock time at either frequency, but the stress applied is different. If it defines cycles, a lower frequency multiplies the time. Plan the outage from the requirement, and record the frequency and duration actually used.
Three architectures cover most of the market, and the choice follows from how varied your cable list is.
| Architecture | Behaviour | Best fit |
|---|---|---|
| Single fixed frequency | One output frequency, one load limit | Short feeders of one class, jointing crews with a narrow scope |
| Three selectable frequencies | 0.1 / 0.05 / 0.02 Hz, with load capability roughly 1.1 / 2.2 / 5.5 µF on a 50 kV platform | Mixed short and medium runs where the operator can choose the frequency from the cable data |
| Automatic sweep | Starts at 0.1 Hz and reduces to as low as 0.01 Hz until the load fits | Varied or unknown cable lists, long feeders, contractors who do not want to compute per job |
Selectable frequencies put the decision on the technician, who must know the capacitance and pick the right setting. Automatic sweep removes that decision but costs more and may hide an error: if the set quietly drops to 0.01 Hz, the test takes longer, and the record must show the frequency actually used. Either way, record the frequency with the result.
Selection guides concentrate on long cables, but short specimens cause their own failure. Below a certain capacitance, the VLF output waveform deteriorates and the test is no longer representative. The threshold is model-specific: the XHDP-50 documentation states that a specimen below 0.05 µF degrades the output waveform and that a 0.05 µF capacitor is connected in parallel to restore it. That figure belongs to that model and should not be read as a universal minimum for all VLF testers.
If your work includes motor windings, short jumpers or switchgear busbars with small capacitance, ask for the minimum load specification of the model under consideration, and confirm whether a parallel capacitor is supplied or is a separate item. The capacitor changes the load seen by the set; it is a deliberate test-circuit measure, not a way of avoiding the set's minimum-load requirement.
These are three different measurements, and a purchase decision should keep them separate.
VLF withstand testing applies a defined AC voltage for a defined time and answers one question: did the insulation survive? The result is pass or fail, and it says nothing about how much life remains.
Tan delta measures dielectric loss as a ratio, indicating the condition of the insulation system. It is temperature and voltage dependent, so it is read as a trend on the same cable under comparable conditions, not as an absolute judgement on a single reading.
Partial discharge measurement detects discharge activity and, depending on the instrument and sensors, can indicate magnitude and phase pattern. Detection is not location. Locating a discharge source requires additional methods - time-domain techniques, multiple sensors, acoustic or TEV detection - and a quieter electromagnetic environment than a substation switchroom usually offers.
DC withstand is a different test, not a diagnostic. It is used where a specification requires it, and it does not provide tan delta or partial discharge information. A set that offers DC output should not be described as offering diagnostics on that basis alone.
The XHDPJ platform is published with AC and DC withstand, tan delta, partial discharge measurement and insulation resistance functions. Which of these are included in a particular configuration, and whether a PD coupler or other accessory is required, should be confirmed for the model and order - the base withstand platform and the diagnostic platform are not the same product.
| Job profile | Voltage rating | Frequency and load | Type |
|---|---|---|---|
| Jointing and repair on 10-15 kV XLPE feeders | 50 kV peak, where the specified test level sits within it | Three selectable frequencies, 1.1-5.5 µF depending on setting | Fixed multi-frequency, light booster |
| Mixed 10-35 kV distribution, varied lengths | 80 kV peak class | Automatic sweep for unknown capacitance | Sweeping withstand set |
| Condition assessment and trending | Set by the highest U0 in the fleet | Sweep plus tan delta, optionally PD | Diagnostic platform |
| Contractor with an unknown future client list | Highest class likely to be sold | Sweep, so new cable types do not force a new purchase | Flexible platform with optional diagnostics |
Keep the table as a starting point. The cable list, the standard applied and the test voltage required decide the rating; the capacitance at that voltage decides the load capability; the client's service expectations decide whether diagnostics are worth paying for.
Choosing a VLF hipot tester is an exercise in reading two numbers together: the test voltage your cables require, and the capacitance the set can energise at that voltage. Voltage rating alone says very little, because the same set will carry much less cable at 80 kV than at 30 kV.
The rest of the decision is about how varied the work is. Fixed frequencies suit a narrow, known scope; selectable frequencies suit crews who will compute per job; automatic sweep suits contractors whose cable list changes. Diagnostics add value only when the service sold includes condition assessment.
XZH TEST manufactures VLF AC hipot systems for medium-voltage cable testing, from fixed multi-frequency sets for jointing crews to sweeping and diagnostic platforms with tan delta and partial discharge options. We size sets against the cable list - voltage class, length and capacitance - rather than against the highest rating in the catalogue.
The rating follows the specified test voltage, converted from RMS to peak, not the cable class alone. As an illustration: 3U0 for an 11 kV cable is 19.05 kV RMS, about 26.9 kV peak, which sits comfortably within a 50 kV set. For a 33 kV cable, 3U0 is 57.3 kV RMS, about 81 kV peak, so a 3U0 test would sit at or beyond a nominal 80 kV rating. But 3U0 is one commonly quoted level under certain acceptance conditions, not a universal requirement; installation, acceptance and maintenance tests may specify different levels, and a lower level can fall within an 80 kV set. Check the edition of IEEE 400.2 in force and the project specification before choosing.
The current a capacitor draws is proportional to voltage and capacitance. At a higher test voltage the same cable draws more current, so the maximum capacitance the set can energise falls. Manufacturer tables reflect this, which is why the capacitance figure must be read at the voltage you intend to use.
0.1 Hz is the common starting point for VLF testing of extruded cable, but the applicable standard and specification decide the frequency and duration, and lower frequencies may be needed to test large capacitance with a given set. Record the frequency actually used, because it affects both the stress application and the comparison with previous tests.
They answer different questions. The withstand test is pass/fail at a defined voltage; tan delta indicates insulation condition and supports trending. If clients buy condition assessment or the same cables are tested periodically, tan delta adds value. If the service is acceptance testing after jointing, it may not be needed.
Often yes, but check the minimum load specification for the model. Below a certain capacitance the output waveform deteriorates; the XHDP-50 documentation, for example, states that a 0.05 µF capacitor is connected in parallel below that threshold. The value is model-specific, so confirm both the threshold and whether the capacitor is supplied.
Test voltage and whether it is RMS or peak, frequency, duration, cable identification and length, measured or calculated capacitance, ambient and conductor temperature where relevant, instrument serial number and calibration status, and the result including any trips. These fields make the test repeatable and comparable.
Send the voltage classes, the longest run of each, the capacitance per kilometre and the test voltage your specification requires. We will calculate the current at 0.1, 0.05 and 0.02 Hz, confirm which rating covers the list, and flag the cases that need a parallel capacitor or a higher-voltage configuration.
Scope note: this article describes selection considerations for VLF test equipment. Test voltages, frequencies, durations and acceptance criteria must be taken from the edition of IEEE 400.2 in force, the cable manufacturer's instructions, the project specification and the asset owner's policy; the levels used here are arithmetic illustrations and are not a restatement of that standard. Capacitance values are examples based on stated assumptions - use measured or data-sheet values for a real test plan. Product data quoted is taken from XZH TEST product documentation at the time of writing and may change; confirm the configuration, output capability at the intended frequency, and accessories with the manufacturer.